APPLIANCE WIRING MATERIAL
Subj.758 Section 1 Page 1298 Issued:1962-04-25
Revised:2011-07-28
Style 1298 Single Conductor with Extruded Insulation and Non-Integral Jacket

Rating80 deg C, 300 Vac, Horizontal flame
ConductorNo. 26-16 AWG, solid or stranded, or No. 27 AWG (7 strands No. 35 AWG)
InsulationPE, 70 mils minimum average thickness, 63 mils minimum thickness at any point.
ShieldIn accordance with Standard
JacketPVC, 30 mils minimum average thickness, 24 mils minimum thickness at any point.
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseFor electronic equipment where insulation is exposed to a temperature not exceeding 80 deg C, and the jacket is exposed to a temperature not exceeding 105 deg C.