| Rating | 105 deg C, 600 Vac, Horizontal flame. Optional - Oil Resistant 60 deg C or 80 deg C. |
|
| Conductor | 8 AWG, stranded. |
|
| Insulation | Extruded PVC, 95 mils min average, 86 mils minimum at any point. |
|
| Standard | Appliance Wiring Material UL 758. |
|
| Marking | General. |
|
| Use | Internal wiring of Electric Air Conditioning and Refrigerating Equipment where exposed to temperatures not exceeding 105 deg C; or Internal Wiring of Electric Air Conditioning and Refrigerating Equipment where exposed to temperatures not exceeding 105 deg C, or where exposed to oil at a temperature not exceeding (60 deg C or 80 deg C, whichever is applicable). |
|