APPLIANCE WIRING MATERIAL
Subj.758 Section 1 Page 1319 Issued:1962-11-26
Revised:2012-09-28
Style 1319 Single Conductor with Extruded Insulation and Non-Integral Extruded Covering

Rating90 or 105 deg C, 600 Vac, Horizontal Flame, Oil Resistant 60 deg C or 80 deg C.
Conductor4 AWG - 2 AWG solid or stranded round, tinned or bare copper, or 4-2 AWG stranded aluminum (90 deg C only).
InsulationExtruded PVC, 40 mils minimum average, 36 mils minimum at any point.
CoveringExtruded Nylon with 6 mil minimum thickness.
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal Wiring of Appliances.