APPLIANCE WIRING MATERIAL
Subj.758 Section 1 Page 1320 Issued:1962-11-26
Revised:2012-09-28
Style 1320 Single conductor with extruded insulation and non-integral extruded covering

Rating90 or 105 deg C, 600 Vac, Horizontal flame, Oil Resistant 60 deg C or 80 deg C.
Conductor1 AWG - 4/0 AWG stranded, tinned or bare copper, rated max 105 deg C, or stranded aluminum, rated max 90 deg C.
InsulationExtruded PVC, 50 mils minimum average, 45 mils minimum at any point.
CoveringExtruded nylon, 7 mils min thickness.
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal Wiring.