APPLIANCE WIRING MATERIAL
Subj.758 Section 1 Page 1339 Issued:1963-08-27
Revised:2014-07-02
Style 1339 Single Conductor with Extruded Insulation

Rating90 deg C, 600 Vac, Horizontal Flame, 60 deg C Wet, 60 deg C Oil.
Conductor4/0 AWG - 500 kcmil, solid or stranded.
InsulationExtruded PVC, 94 mils minimum average thickness, 85 mils minimum thickness at any point. Recognized QMTT2 PVC Insulation Compound suitable for use in Type TW.
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal Wiring.