APPLIANCE WIRING MATERIAL
Subj.758 Section 1 Page 1347 Issued:1963-10-16
Revised:2014-03-14
Style 1347 Single conductor with insulation

Rating80 deg C, 300 Vac, Horizontal flame.
Conductor26 AWG - 16 AWG, solid or stranded.
InsulationExtruded PVC, 16 mils minimum average thickness, 13 mils minimum thickness at any point.
ShieldConductive thermoplastic, aluminum-faced Polyester, copper braid or wrap, or equivalent; optional uninsulated drain wire.
JacketExtruded PVC, 16 mils minimum average thickness, 13 mils minimum thickness at any point.
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal wiring.

UL and the UL Logo are trademarks of UL LLC © 2024