Rating | 105 deg C, 600 Vac, Horizontal Flame. |
|
Conductor | 30 AWG - 1000 kcmil, solid or stranded. |
|
Insulation | Extruded XLPVC. |
| Conductor size | Minimum average thickness | Minimum thickness at any point |
| 30-9 AWG | 30 mils | 27 mils |
| 8 AWG | 45 mils | 41 mils |
| 7-2 AWG | 60 mils | 54 mils |
| 1-4/0 | 78 mils | 70 mils |
| 250-500 kcmil | 95 mils | 86 mils |
| 501-1000 kcmil | 110 mils | 99 mils |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | For use as motor leads or internal wiring of appliances.
Tags may indicate the following: 2500 Volts Peak - For Electronic Use Only. |
|