Style 1563 Single conductor using non-integral jacket.

Rating60 deg C, 600 Vac, Horizontal flame.
Conductor14 AWG - 10 AWG, solid or stranded.
InsulationRecognized Component QMTT2 Extruded PVC insulation compound suitable for use in Type TW, 30 mils minimum average thickness, 27 mils minimum thickness at any point.
ShieldBare Copper braid. Combination of strand size and number such that the braid is equivalent to 16 AWG.
CoveringExtruded nylon 3 mils minimum thickness, over insulation.
JacketExtruded PVC, 20 mils minimum average, 16 mils minimum at any point.
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseAs factory assembled Nonheating Leads on Deicing units for use in concrete or asphalt driveway, walk, etc.