APPLIANCE WIRING MATERIAL
Subj.758 Section 1 Page 1702 Issued:1976-10-28
Revised:2012-11-09
Style 1702 Single conductor with extruded insulation

Rating105 deg C, 600 Vac, VW-1 flame.
Conductor24 AWG - 4/0 AWG, stranded or braided.
InsulationExtruded PVC.
Conductor SizeMinimum Average thicknessMinimum Thickness at any Point
24-9 AWG30 mils27 mils
8 AWG45 mils40 mils
7-2 AWG60 mils54 mils
1-4/0 AWG80 mils72 mils
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal Ground Strap Wire for Audio, Video and Electronic Equipment.