APPLIANCE WIRING MATERIAL
Subj.758 Section 1 Page 1705 Issued:1976-11-18
Revised:2012-04-09
Style 1705 Single conductor with extruded insulation.

Rating150 deg C, 600 Vac, Horizontal flame.
Conductor30 AWG - 4/0 AWG, solid or stranded, tinned, silver plated or nickel coated copper, nickel conductor, silver plated zirconium copper alloy, silver plated cadmium chrome copper alloy, silver plated cadmium bronze copper alloy, or silver plated copper-clad steel.
InsulationExtruded ECTFE.
Conductor sizeMinimum average thicknessMinimum thickness at any point
30-10 AWG20 mils18 mils
8-2 AWG30 mils27 mils
1-4/0 AWG45 mils40 mils
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal wiring. Tags may indicate the following: 2500 Volts Peak - For Electronic Use only.

UL and the UL Logo are trademarks of UL LLC © 2024