Rating | 125 deg C, 600 Vac, Horizontal flame. |
|
Conductor | 30 AWG - 4/0 AWG solid or stranded round, tinned or bare - min 90% conductivity. |
|
Insulation | Extruded TPE |
| AWG Conductor Size | Minimum average thickness (mils) | Minimum thickness at any point (mils) |
| 30-9 | 30 | 27 |
| 8 | 45 | 40 |
| 7-2 | 60 | 54 |
| 1-4/0 | 80 | 64 |
|
Covering | (Optional) Braid. |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | For use as Motor Leads or Internal Wiring of Appliances. Tags may indicate the following: 2500 V Peak - For Electronic Use Only. |
|