APPLIANCE WIRING MATERIAL
Subj.758 Section 1 Page 1778 Issued:1979-02-28
Revised:2012-04-27
Style 1778 Single-conductor wire using non-integral jacket.

Rating80 deg C, 300 Vac, Horizontal flame.
Conductor30 AWG - 16 AWG, solid or stranded.
InsulationExtruded XLPE, 16 mils minimum average thickness, 13 mils minimum thickness at any point.
ShieldOptional.
CoveringOptional - Extruded PVC, extruded SRPVC, 8 mils minimum thickness, Nylon (Polyamide), 2 mils minimum thickness, or a fibrous braid.
JacketExtruded PVC, 30 mils minimum average thickness, 27 mils minimum thickness at any point.
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal or external wiring.