APPLIANCE WIRING MATERIAL
Subj.758 Section 1 Page 1816 Issued:1980-02-15
Revised:2011-10-11
Style 1816 Single-conductor cable using non-integral jacket

Rating80 deg C, 300 Vac, Horizontal flame.
Conductor30 AWG - 4/0 AWG solid or stranded.
InsulationExturded PVC
30-16 AWG conductor size15 mils min average13 mils minimum at any point
15-10 AWG30 avg27 min
9-8 AWG45 avg40 min
7-2 AWG60 avg54 min
1-4/0 AWG80 avg72 min
ShieldBraid or spiral wrap construction using steel, nickel-tin, or copper-plated steel, or copper-plated iron alloy, or copper-plated nickel wires.
JacketExtruded PVC
30-16 AWG conductor size15 mils min average12 mils minimum at any point
5-2 AWG30 avg27 min
4/0 AWG45 avg40 min
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal wiring of Electronic equipment where not subjected to repeated flexing in end application.

UL and the UL Logo are trademarks of UL LLC © 2024