Rating | 60 or 80 deg C, 30 Vac, Horizontal flame. |
|
Conductor | 20 AWG - 4/0 AWG consisting of 34 AWG or smaller strands. |
|
Insulation | Extruded PVC |
| 20-16 AWG conductor size | 15 mils min average | 13 mils min at any point |
| 15-9 AWG | 20 avg | 17 min |
| 8-2 AWG | 30 avg | 27 min |
| 1-1/0 AWG | 40 avg | 36 min |
| 2/0-4/0 AWG | 48 avg | 43 min |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | Ground strap lead wire for electronic equipment where the acceptability of the combination is to be determined by Underwriters Laboratories Inc. |
|