Rating | 60, 80, 90, 105 deg C, 30 Vac, VW-1 flame. |
|
Conductor | 40 AWG minimum-Material not specified. |
|
Insulation | Labeled or complying with manufacturer's AWM procedure. Minimum rating of insulated singles equals or exceeds rating of cable. |
|
Assembly | Two or more twisted singles or groups of twisted singles twisted together. Lay not specified. Barrier layer and/or fillers optional. Manufacturer shall maintain a complete description of each assembly. Two or three conductors may be laid parallel to form flat cable. |
|
Shield | Optional. |
|
Jacket | PVC |
| dia of cable |
| 0.425 inches or less | 30 mils min average | 24 mils minimum at any point |
| 0.426-0.700 dia | 60 avg | 48 min |
| 0.701-1.500 dia | 80 avg | 64 min |
| 1.501-2.500 dia | 110 avg | 88 min |
| 2.501 dia and larger | 140 avg | 112 min |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | Internal or External wiring of Class 2 systems |
|