Rating | 105 deg C, 600 Vac, Cable flame. |
|
Insulation | Labeled or complying with manufacturer's AWM Procedure. The designations of all styles of individual conductors used in making up the cable assembly shall be available. |
|
Assembly | Two or more individually insulated conductors or groups of insulated conductors cabled together. All conductors in any group twisted together. If more than one group is used, groups shall also be twisted together. The length of lay of the twisted conductors or groups is not specified. Fillers may be used in a cable but are not required. A barrier layer, if employed, may be a fibrous wrap serving; braid, Nylon, oriented PETP or a thermoplastic jacket (4 mil minimum thickness at any point) or tape wrap. Such a barrier layer would serve to protect the cable during further processing and would be applied over the twisted assembly of individual conductors or groups of conductors. |
|
Covering | Optional - Extruded PVC, 15 mils minimum average thickness, 13 mils minimum thickness at any point. May be extruded over the conductor assembly. |
|
Shield | Optional. |
|
Jacket | Extruded XLPE |
| Diameter of core assembly under jacket | Minimum average thickness | Minimum thickness at any point |
| 0.425 inch or less | 30 mils | 24 mils |
| 0.426 - 0.700 inch | 45 mils | 36 mils |
| 0.701 - 1.000 inch | 60 mils | 48 mils |
| 1.001 - 1.500 inches | 80 mils | 64 mils |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | External Interconnection or internal wiring of electronic equipment. |
|