APPLIANCE WIRING MATERIAL
Subj.758 Section 2 Page 20017 Issued:1979-07-03
Revised:2011-10-06
Style 20017 Parallel cable with extruded integral insulation.

Rating80 deg C, 300 Vac, VW-1 flame.
Conductor28 AWG - 18 AWG, solid or stranded.
InsulationIntegral with Jacket. Extruded PVC, 60 mils min average, 54 mils minimum at any point.
AssemblyTwo, three or four conductors.
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal wiring of Electronic Equipment and Interconnecting Loudspeakers. Tags may indicate the following: 600 Volts Peak - For Electronic Use only.