APPLIANCE WIRING MATERIAL
Subj.758 Section 2 Page 20031 Issued:1979-11-20
Revised:2012-07-23
Style 20031 Multiple-conductor cable using non-integral jacket

Rating75 deg C, 600 Vac, FT2 flame, Oil Resistant 60 deg C.
Conductor18 AWG - 2 AWG solid or stranded round, tinned or bare copper.
InsulationExtruded FEP or PE or PVC, 30 mils min average, 27 mils minimum at any point.
AssemblySame as type STO Cord.
JacketExtruded PVC, 60 mils min average, 48 mils minimum at any point.
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal Wiring or External Interconnection.

UL and the UL Logo are trademarks of UL LLC © 2024