APPLIANCE WIRING MATERIAL
Subj.758 Section 2 Page 20047 Issued:1980-03-31
Revised:2019-11-07
Style 20047 Multiple-conductor cable using non-integral jacket

Rating105 deg C, 300 Vac, Horizontal flame, Oil Resisitant 60 or 80 deg C, Moisture Resistant and Gasoline Resistant 75 deg C.
Conductor26 AWG - 12 AWG solid or stranded, tinned or bare copper. May use same or mixed AWG size.
InsulationLabeled or complying with Manufacturer's AWM Procedure.
AssemblyConsists of two or more conductors, twisted pairs or groups of twisted conductors twisted together. The conductors or groups of conductors may be laid parallel forming a flat, oval or round cable. A barrier layer and/or fillers are optional. Manufacturer shall maintain a complete description of each assembly.
ShieldOptional.
CoveringInner - (Optional) A 6 mil or heavier Extruded PVC covering may be extruded over the conductor assembly.
JacketExtruded Nylon
dia of the cable under jacket
0.351-0.450 inches or less*4 mils minimum thickness at any point
0.351-0.450 dia5 min
0.451-0.550 dia6 min
0.551-0.750 dia7 min
0.751-0.950 dia8 min
*Major diameter of cable is flat or oval.
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal wiring.