| Rating | 80 deg C, 30 Vac, Horizontal Flame, Cable Flame. |
|
| Insulated Conductor | Labeled or complying with manufacturer's AWM procedure. May use same or mixed AWG size. |
|
| Assembly | Consists of two or more insulated conductors, twisted pairs or groups of twisted insulated conductors twisted together. The insulated conductors or groups of insulated conductors may be laid parallel forming a flat, oval or round cable. The lay of the insulated conductors is not specified. A barrier layer and/or fillers are optional. Manufacturer shall maintain a complete description of each assembly. |
|
| Covering | Optional - A 6 mil or heavier PVC covering may be extruded over the conductor assembly. |
|
| Shield | Optional. |
|
| Jacket | Extruded PVC. |
| Diameter of core assembly under jacket | Minimum average thickness | Minimum thickness at any point |
| 0.700 inch or less | 30 mils | 24 mils |
| 0.701-1.000 | 60 mils | 48 mils |
| 1.001-1.500 | 80 mils | 64 mils |
|
| Standard | Appliance Wiring Material UL 758. |
|
| Marking | General. |
|
| Use | Internal wiring and external interconnection in Class 2 circuits of electronic equipment. |
|