APPLIANCE WIRING MATERIAL
Subj.758 Section 2 Page 20083 Issued:1980-09-03
Revised:2011-09-15
Style 20083 Multiple-conductor cable using non-integral jacket

Rating80 deg C, 30 Vac, Horizontal Flame, Cable Flame.
Insulated ConductorLabeled or complying with manufacturer's AWM procedure. May use same or mixed AWG size.
AssemblyConsists of two or more insulated conductors, twisted pairs or groups of twisted insulated conductors twisted together. The insulated conductors or groups of insulated conductors may be laid parallel forming a flat, oval or round cable. The lay of the insulated conductors is not specified. A barrier layer and/or fillers are optional. Manufacturer shall maintain a complete description of each assembly.
CoveringOptional - A 6 mil or heavier PVC covering may be extruded over the conductor assembly.
ShieldOptional.
JacketExtruded PVC.
Diameter of core assembly under jacketMinimum average thicknessMinimum thickness at any point
0.700 inch or less30 mils24 mils
0.701-1.00060 mils48 mils
1.001-1.50080 mils64 mils
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal wiring and external interconnection in Class 2 circuits of electronic equipment.