Style 20125 Multiple-conductor cable using non-integral jacket

Rating80, 90, 105 deg C, 30 Vac, VW-1 flame.
Conductor50 AWG minimum - material not specified.
InsulationExtruded FRPE or PE or TPES or PVC, 2 mils minimum average thickness. Solid or cellular.
AssemblyTwo or more twisted singles or groups of twisted singles twisted together. Lay not specified. Barrier layer and/or fillers optional. Two or three conductors and/or conductor groups may be laid parallel to form flat cable. Manufacturer shall maintain a complete description of each assembly.
ShieldOptional.
Covering(Optional) Extruded PVC, polyamide or polyester or lacquered braid.
JacketExtruded PVC
dia of cable under jacket
0.425 inches or less30 mils min average24 mils min at any point
0.426-0.700 dia60 avg48 min
0.701-1.500 dia80 avg64 min
1.501-2.500 dia110 avg88 min
2.501 dia and larger140 avg112 min
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal or external wiring of Class 2 systems of electronic equipment. Cable must be terminated with connector at each end.