APPLIANCE WIRING MATERIAL
Subj.758 Section 2 Page 20136 Issued:1981-04-29
Revised:2012-04-17
Style 20136 Multiple-conductor cable using non-integral jacket

Rating80 deg C, 50 Vac, VW-1 flame.
Conductor40 AWG - 20 AWG, solid or stranded.
InsulationExtruded FRPE, extruded PE, extruded PVC, extruded XLPE, extruded XLPVC, extruded foamed FRPE, extruded foamed PE or extruded foamed XLPE, 5 mils minimum average thickness, 4 mils minimum thickness at any point.
AssemblyTwo to 20 conductors, twisted singles or groups of twisted singles cabled together, lay not specified. Fillers and/or barrier layer optional.
ShieldOptional.
JacketExtruded PVC, 5 mils minimum average thickness, 4 mils minimum at any point.
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UsePick up lead of video disc in Class 2 circuits (Less than 15 W where cable is within the enclosure and not subject to abrasion.)