APPLIANCE WIRING MATERIAL
Subj.758 Section 2 Page 20162 Issued:1982-01-28
Revised:2012-04-13
Style 20162 Parallel Wire

Rating105, 250 Vac, Horizontal flame, Moisture Resistant 75 deg C.
Conductor1.75 mils dia resistance wire wound for a min of 25 turns per in on a Rayon, Cotton, Polyester, Fiberglass, Nylon yarn core, Nickel, Copper Alloy or Copper, size varies dependent upon wattage demand.
InsulationPVC, 45 mils min average, 40 mils minimum at any point. Distance between conductors 7/16 in =/- 1/16 in Web thickness 1/32 in min. Web may have additional rib. See Facing Page for Compound.
AssemblyTwo conductors
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseFor heat tracing of pipes in industrial or commercial installations only.