APPLIANCE WIRING MATERIAL
Subj.758 Section 2 Page 20207 Issued:1982-10-22
Revised:2012-07-25
Style 20207 Multiple-Conductor Cable using Non-Integral Extruded Jacket

Rating80 deg C, 600 Vac, Cable Flame.
Conductor40 AWG minimum, Solid or Stranded Round. May use same or mixed AWG size.
InsulationLabeled or complying with manufacturer's AWM procedure.
AssemblyConsists of two or more conductors, twisted pairs or groups of twisted conductors twisted together. The conductors or groups of conductors may be laid parallel forming a flat, oval or round cable. The lay of the conductors is not specified. A barrier layer and/or fillers are optional. Manufacturer shall maintain a complete description of each assembly.
CoveringOptional - Extruded PVC, 6 mil minimum at any point may be extruded over the conductor assembly.
JacketExtruded PVC
diameter of cable under jacket in inches*mils minimum averagemils minimum at any point
0.700 or less3024
0.701-1.0006048
1.001-1.5008064
*Major diameter if cable is flat or oval.
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseExternal interconnection or internal wiring.