Rating | 80 deg C, 30 Vac, Horizontal flame. |
|
Conductor | 30 AWG - 16 AWG, solid or stranded. |
|
Insulation | Extruded XLPE, 8 mils minimum average thickness, 6 mils minimum thickness at any point. |
|
Assembly | Two or more conductors. |
|
Shield | Optional. |
|
Jacket | PVC |
| Diameter of core assembly under jacket | Minimum average thickness | Minimum thickness at any point |
| 0.350 inch or less | 15 mils | 12 mils |
| 0.351-0.700 inch | 30 mils | 23 mils |
| 0.701-1.000 inch | 45 mils | 36 mils |
| 1.001-1.500 inch | 60 mils | 48 mils |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | Internal Wiring of Class 2 Circuits In Electronic Equipment. |
|