Rating | 80 deg C, 300 Vac, Cable flame. |
|
Conductor | 36 AWG min, Solid or Stranded. |
|
Insulation | Labeled or complying with manufacturer's AWM Procedure. |
|
Assembly | Two or more individually insulated conductors or groups of insulated conductors cabled together to form a round cable. A flat or oval cable may also be constructed with not more than three rows of single conductors or groups of conductors. The length of lay of the twisted conductors or groups is not specified. Fillers may be used in a cable but are not required. A barrier layer, if employed, may be a fibrous wrap serving, or braid, paper, nylon, oriented polyethylene terephthalate, or thermoplastic-tape wrap. Such a barrier layer would serve to protect the cable during further processing and would be applied immediately over the twisted assembly of individual conductors or groups of conductors or over the shield, if provided. |
|
Covering | Optional. |
|
Shield | Optional. |
|
Jacket | Extruded TPU. |
| Diameter of core assembly under jacket inch | Minimum average mils | Minimum at any point mils |
| 0.700 or less | 30 | 24 |
| 0.701-1.000 | 45 | 36 |
| 1.001-1.500 | 60 | 48 |
| 1.501-2.500 | 80 | 64 |
| 2.501-4.000 | 110 | 88 |
| 4.001 and larger | 140 | 112 |
| *Major dia if cable is flat or oval. |
|
Braid | Optional. |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | External interconnection of electronic equipment. |
|