Rating | 80 deg C, no voltage assigned, Cable flame. |
|
Insulation | Labeled or complying with manufacturer's AWM procedure. |
|
Assembly | Two to fifty conductors; different conductor sizes may be used in one cord. Two to eight conductors may be laid parallel or twisted together. Nine or more conductors shall be twisted together. Lay of insulated conductors not specified, but with a twist opposite in direction to the direction in which the helical cord in wound. Cable may be either straight or coiled or in the form of a helix. |
|
Shield | Optional. |
|
Jacket | Extruded TPU. |
| dia of cable under jacket in inches | Min. Average thickness in mils | Min. thickness at any point mils |
| 0.425 or less | 30 | 24 |
| 0.426-0.700 | 45 | 36 |
| 0.701-1.500 | 60 | 48 |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | Internal wiring. |
|