APPLIANCE WIRING MATERIAL
Subj.758 Section 2 Page 20371 Issued:1985-01-25
Revised:2012-11-26
Style 20371 Multiple-conductor cable using non-integral jacket

Rating200 deg C, 30 Vac, Cable flame. Optional - 80 deg C Oil.
Insulated ConductorLabeled or complying with manufacturer's AWM procedure.
AssemblyTwo or more individually insulated conductors or groups of insulated conductors cabled together. All conductors in any group twisted together. If more than one group is used, groups shall also be twisted together. The length of lay of the twisted conductors or groups is not specified. A barrier layer, if employed, may be of fibrous wrap serving, or braid; paper; nylon (polyamide); PET; or thermoplastic-type wrap. Such a barrier layer would serve to protect the cable during further processing and would be applied immediately over the twisted assembly of individual conductors or groups of conductors.
ShieldOptional.
JacketExtruded FEP.
Diameter of cable core assembly under jacketMinimum average thicknessMinimum thickness at any point
0.425 inch or less25 mils20 mils
0.426-0.700 inch30 mils24 mils
0.701-1.500 inch45 mils36 mils
1.501-2.500 inch60 mils48 mils
2.501 inch and larger80 mils64 mils
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseExternal interconnection or internal wiring of appliances or electronic equipment.

UL and the UL Logo are trademarks of UL LLC © 2024