APPLIANCE WIRING MATERIAL
Subj.758 Section 2 Page 20376 Issued:1985-02-26
Revised:2012-05-22
Style 20376 Multiple-Conductor Cable using Non-Integral Extruded Jacket

Rating105 deg C, 600 Vac, Cable Flame.
Conductor36 AWG min, Solid or Stranded Round.
InsulationLabeled or complying with manufacturer's AWM procedure
AssemblyTwo or more individually insulated conductors or groups of insulated conductors cabled together to form a round cable. A flat or oval cable may also be constructed with not more than three rows of single conductors or groups of conductors. The length of lay of the twisted conductors or groups is not specified. Fillers may be used in a cable but are not required. A barrier layer, if employed, may be of fibrous wrap serving, or braid; paper; nylon; oriented polyethylene terephthalate; or thermoplastic-type wrap. Such a barrier layer would serve to protect the cable during further processing and would be applied immediately over the twisted assembly of individual conductors or groups of conductors.
ShieldOptional.
JacketExtruded TPU
diameter of cable under jacket in inches*mils minimum averagemils minimum at any point
0.700 or less4536
0.701-1.0006048
1.001-1.5008064
1.501-2.50011088
2.500 and larger140112
*Major dia if cable is flat or oval.
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseExternal Interconnection of electronic equipment.

UL and the UL Logo are trademarks of UL LLC © 2024