APPLIANCE WIRING MATERIAL
Subj.758 Section 2 Page 20384 Issued:1985-03-25
Revised:2019-11-07
Style 20384 Multiple Conductor Cable with Extruded Non-integral Jacket.

Rating105 deg C, 300 Vac, Horizontal flame, Oil Res 60 or 80 deg C, Moisture Res 75 deg C
InsulationLabeled or complying with with manufacturers AWM procedure.
AssemblyTwo or more twisted singles or groups of twisted singles twisted together, same as for type SJTO. Lay not specified. Barrier layer and/or fillers optional. Manufacturer shall maintain complete description of each assembly. May use mixed sizes of insulated singles.
Shield(Optional) - May be over one or more of the insulated conductors or applied over assembly.
JacketExtruded PVC
dia of cable under jacket
0.700 inches or less30 mils min average24 mils minimum at any point
0.701-1.000 dia45 avg36 min
1.001-1.500 dia60 avg48 min
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal wiring.

UL and the UL Logo are trademarks of UL LLC © 2024