| Rating | 105 deg C, 300 Vac, Horizontal flame. |
|
| Conductor | 30 AWG - 16 AWG, solid or stranded. |
|
| Insulation | Labeled or complying with manufacturer's AWM Sec. 1 procedure. |
|
| Assembly | Two to 200 insulated singles, twisted pair, triads or quads laid parallel in one plane, bonded together or to a PVC-Polyester or extruded PVC covering in such a fashion to form a flat ribbon-type cable. May include mixed AWG sizes. Sections may be slit into singles or groups of conductors. |
|
| Shield | Optional. |
|
| Covering | Optional. Extruded PVC, 5 mils min at any point, 80 mils max. |
|
| Standard | Appliance Wiring Material UL 758. |
|
| Marking | General. |
|
| Use | Internal wiring of electronic equipment (such as computers and electric business machines). |
|