Rating | 75 deg C, 300 Vac, Cable flame. |
|
Conductor | 36 AWG - 4/0 AWG, solid or stranded. |
|
Insulation | Extruded PVC |
| Conductor size | Minimum average thickness in mils | minimum thickness at any point |
| 36-10 AWG | 20 | 18 |
| 9-7 AWG | 30 | 27 |
| 6-2 AWG | 45 | 40 |
| 1-4/0 AWG | 60 | 54 |
|
Assembly | Two or more twisted singles or groups of twisted singles twisted together or groups may be laid parallel to form flat, oval or round cable. Lay not specified. Barrier layer and/or fillers optional, manufacturer shall maintain a complete description of each assembly. May use same or mixed AWG size. |
|
Shield | Optional. |
|
Covering | Optional - Extruded PVC, 5 mils thickness may be extruded over the conductor assembly. |
|
Shield | Optional. |
|
Jacket | PVC |
| dia of cable under jacket in inch | Mimum average thickness in mils | Mimum thickness at any point in mils |
| 0.700 or less | 30 | 24 |
| 0.701-1.000 | 45 | 36 |
| 1.001-1.500 | 60 | 48 |
| 1.501-2.500 | 80 | 64 |
| 2.501-4.000 | 110 | 88 |
| 4.001 dia and larger | 140 | 112 |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | Internal or external wiring. |
|