Rating | 80 deg C, 30 Vac, Cable flame. |
|
Insulation | Labeled or complying with manufacturer's AWM Procedure. |
|
Assembly | Two or more singles, twisted pairs of groups of twisted singles, cabled together or groups may be laid parallel to form flat, oval, or round cable. Lay not specified. Barrier layer and/or fillers optional. Manufacturer shall maintain a complete description of each assembly. May use same or mixed AWG size. |
|
Shield | Optional. |
|
Covering | Optional - A 5 mil or heavier PVC covering may be extruded over the conductor assembly. |
|
Jacket | SRPVC. |
| Dia of cable under jacket | Minimum average | Minimum at any point |
| 0.425 inch or less | 20 mils | 16 mils |
| 0.426-0.700 inch | 30 mils | 24 mils |
| 0.701-1.000 inch | 40 mils | 36 mils |
| 1.001-1.500 inch | 50 mils | 40 mils |
| 1.501-2.500 inch | 60 mils | 48 mils |
| 2.501 inch and larger | 80 mils | 64 mils |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | Internal Wiring or External Interconnection of Electronic Equipment. |
|