Rating | 90 deg C, 30 Vac, Horizontal flame. |
|
Conductor | 40 AWG min. Material not specified. |
|
Insulation | Labeled or complying with manufacturer's Procedure, or see Use statement. |
|
Assembly | Two or more twisted singles or groups of twisted singles twisted together or groups may be laid parallel to form flat, oval, or round cables. Lay not specified. Barrier layer and/or fillers optional. Manufacturer shall maintain a complete description of each assembly. |
|
Shield | Optional - May be over one or more of the insulated conductors or applied over the assembly. |
|
Covering | Optional. |
|
Jacket | Extruded TPU - See facing page for compound |
| dia of cable under jacket |
| 0.250 inches or less | 15 mils min average | 13 mils min at any point |
| 0.251-0.424 dia | 30 avg | 24 min |
| 0.425-0.700 dia | 45 avg | 36 min |
| 0.701-1.000 dia | 80 avg | 64 min |
| 1.001-2.500 dia | 110 avg | 88 min |
| 2.501 dia and larger | 140 avg | 112 min |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | No. 1A Internal wiring in Class 2 circuits of electronic equipment where each end is terminated in connectors. or Use No. 1B Cables using 30 mils or greater jacket thickness only: External interconnection or internal wiring in Class 2 circuits of electronic equipment where each end is terminated in connectors. Use No. 2A Internal wiring in Class 2 circuits of electronic equipment or external interconnection in Class 2 circuits of electronic equipment where not routed along walls, floors, or other abuse areas. or Use No. 2B Cables using 30 mils or greater jacket thickness only: External interconnection or internal wiring in Class 2 circuits of electronic equipment. |
|