Rating | 60, 75, 90, 105 deg C, 300 Vac, FT2 flame. |
|
Conductor | 18 AWG - 10 AWG or smaller stranded, tinned or bare copper. |
|
Insulation | PVC |
| 18-16 AWG conductor size | 30 mils min average | 27 mils minimum at any point |
| 15-14 AWG | 40 avg | 36 min |
| 13-12 AWG | 45 avg | 41 min |
| 11-10 AWG | 55 avg | 50 min |
|
Assembly | Two to three conductors, Same as non-integral SPT cords except for thicknesses, etc., outlined on this Style Page. |
|
Jacket | PVC |
| 18-16 AWG conductor size | 30 mils min average | 24 mils minimum at any point |
| 15-14 AWG | 40 avg | 30 min |
| 13-12 AWG | 50 avg | 38 min |
| 11-10 AWG | 55 avg | 42 min |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | Internal or external wiring of appliances. |
|