APPLIANCE WIRING MATERIAL
Subj.758 Section 2 Page 20603 Issued:1988-12-29
Revised:2012-03-21
Style 20603 Multiple-Conductor Cable Using Non-Integral Jacket

Rating80 deg C, 300 Vac, Cable flame.
Conductor36 AWG - 4/0 AWG solid or stranded.
InsulationExtruded PVC
AWG conductor sizeminimum average thickness in milsminimum thickness at any point in mils
36-102220
9-73037
6-24540
1-4/06054
AssemblyTwo or more twisted singles or groups of twisted singles twisted together or groups may be laid parallel to form flat, oval or round cable. Lay not specified. Barrier layer and/or fillers optional. May use same or mixed AWG size.
ShieldOptional.
CoveringOptional - A 10 mil thick or heavier PVC covering may be extruded over the conductor assembly.
JacketExtruded PVC
*Diameter of cable under jacketminimum average thickness in milsminimum thickness at any point in mils
0.700 inches or less3024
0.701-1.0004536
1.001-1.5006048
1.501-2.5008064
2.501-4.00011088
4.001 inches and larger140112
* Major diameter if cable is flat or oval.
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal or external interconnections of electronic equipment and appliances.

UL and the UL Logo are trademarks of UL LLC © 2024