Rating | 105 deg C, 300 Vac, Cable flame. Optional - Oil Resistant 60 deg C. |
|
Conductor | 40 AWG min, solid or stranded. |
|
Insulation | Labeled or complying with Manufacturer's AWM Procedure. |
|
Assembly | Same as for Type SVTO. Consists of two or more singles, twisted pairs or groups of twisted singles twisted together. The singles or groups of singles may be laid parallel forming a flat, oval or round cable. The lay of the conductors is not specified. A barrier layer and/or fillers are optional. Manufacturer shall maintain a complete description of each assembly. May use same or mixed AWG size. |
|
Shield | Optional. |
|
Covering | Optional - A 6 mil or heavier thermoplastic covering may be extruded over the conductor assembly. |
|
Jacket | Extruded PVC |
| dia of cable under jacket is 0.700 inches or less* | 30 mils min average | 24 mils minimum at any point |
| 0.701-1.000 in | 45 avg | 36 min |
| 1.001-1.500 in | 60 avg | 48 min |
| 1.501-2.500 in | 80 avg | 64 min |
| 2.501-4.000 in | 110 avg | 88 min |
| 4.001 in and larger | 140 avg | 112 min |
| *Major diameter if cable is flat or oval. |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | External interconnection of electronic equipment and/or appliances. Tags may also indicate the following: 600 V Peak for Electronic Use Only, or Jacket Suitable for 60 deg C Immersion in Oil. |
|