Rating | 80 deg C, 30 Vac, Cable flame. |
|
Insulation | Labeled or complying with manufacturer's AWM procedure. |
|
Assembly | Multi conductors. A barrier layer and/or fillers are optional. |
|
Shield | Optional. |
|
Covering | Optional. A 6 mil or heavier PVC covering may be extruded over the conductor assembly. |
|
Jacket | Extruded PVC |
| major dia in inches |
| 0.350 or less | 20 mils min average | 16 mils minimum at any point |
| 0.351-0.700 in | 30 avg | 24 min |
| 0.701-1.000 in | 40 avg | 36 min |
| 1.001-1.500 in | 54 avg | 48 min |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | Internal Wiring of electronic equipment in Class 2 circuits only. Styles using 30 mils average jacket thickness may be tag marked for external interconnection of electronic equipment in Class 2 circuits only. |
|