Rating | 80 deg C, 300 Vac. Horizontal Flame. |
|
Conductor | 20 AWG - 16 AWG consisting of No. 34 AWG or smaller stranded. |
|
Insulation | Extruded PVC, 30 mils minimum average thickness, 27 mils minimum thickness at any point, Individual conductor insulations may be colored for circuit identification. |
|
Assembly | Seven Conductor laid flatwith overall jacket. Several different conductors sizes may be employed in one cable within this size range. The jacket shall fill the valleys between adjacent conductors. Adjacent conductors shall be separated into groups of not more than four each by 23 mil minimum web extruded integral with jacket. |
|
Jacket | Extruded PVC, 45 mils minimum average thickness, 36 mils minimum thickness at any point and a nominal 30 mil wall compound along the sides of the cable |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | For use as Television Remote Cable where exposed to temperatures not exceeding 80 deg C. |
|