| Rating | 75 deg C, 600 Vac, Cable flame. |
|
| Conductor | 14 AWG - 2000 kcmil solid or stranded round, tinned or bare copper. |
|
| Insulation | FRPE |
| 14-2 AWG conductor size | 60 mils min average | 54 mils minimum at any point |
| 1-4/0 AWG | 80 avg | 72 min |
| 250-500 kcmils | 95 avg | 86 min |
| 550-1000 kcmils | 110 avg | 99 min |
| 1100-2000 kcmils | 125 avg | 112 min |
|
| Assembly | Two or more insulated conductors, twisted pairs or groups of twisted singles twisted together to form a round or oval cable. The lay of the conductors are not specified. Cable may employ optional fillers and may use the same or mixed conductor sizes. |
|
| Shield | Optional. |
|
| Covering | Optional. PVC; extruded over the conductor assembly. |
|
| Jacket | PE |
| dia in inches |
| 0.425 o less | 45 mils min average | 36 mils minimum at any point |
| 0.426-0.700 in | 60 avg | 48 min |
| 0.701-1.500 in | 80 avg | 64 min |
| 1.501-2.500 in | 110 avg | 88 min |
| 2.500 in and larger | 140 avg | 112 min |
|
| Standard | Appliance Wiring Material UL 758. |
|
| Marking | General. |
|
| Use | External interconnection of electronic equipment or appliances. |
|