Rating | 150, 200 deg C, 600 Vac, Horizontal flame. |
|
Conductor | 18 AWG - 12 AWG, stranded only. |
|
Insulation | FEP, 10 mils min average, 9 mils minimum at any point. |
|
Assembly | Over two FEP insulated conductors laid parallel, a 10 mil min avg, wall of FEP is extruded to form a two conductor parallel cord. This cord is now prepared for the spiral wound heating element. This is done by carefully removing the FEP insulation along the length of the cord so as to bare the copper conductor for approx 1/2 in widths at periodic intervals. A spirally wound nichrome or other types of resistance wire is then carefully wound the length of the core, and may be soldered to the exposed conductor. By varying the distance between contacts with the conductors, the number of turns per inch of resistance wire and the AWG size (resistance) of the spirally wound wire, different wattages per foot per service voltage can be obtained. |
|
Shield | Optional. |
|
Covering | Optional. 13 mils min at any point of extruded special copolymer of ethylene and tetrafluoroethylene (ETFE). See Facing Page for Compound Designation or FEP. |
|
Jacket | ETFE, 30 mils min average. See Facing Page for Compound Designation. |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | Pipe heating cable where the acceptability of the combination is to be determined by UL LLC. |
|