Rating | 80 deg C, 300 Vac, Cable flame. |
|
Insulation | Labeled or complying with manufacturer's AWM Procedure. |
|
Assembly | Two or more singles, twisted pairs or groups of twisted singles twisted together or singles or groups of singles may be laid parallel to form flat, oval or round cable. Lay not specified. Barrier layer and/or fillers optional. Manufacturer shall maintain a complete description of each assembly. May use same or mixed AWG size. |
|
Shield | Optional. |
|
Covering | Optional. A 6 mil or heavier PVC covering may be extruded over the conductor assembly. |
|
Jacket | CPE |
| dia. in inches |
| 0.700 or less | 30 mils min average |
| 0.701-1.000 dia | 45 avg |
| 1.001-1.500 dia | 60 avg |
| 1.501-2.500 dia | 80 avg |
| 2.501-4.000 dia | 110 avg |
| 4.001 dia and larger | 140 avg |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | Internal wiring or external interconnection of electronic equipment. |
|