APPLIANCE WIRING MATERIAL
Subj.758 Section 2 Page 20874 Issued:1994-10-18
Revised:2011-12-05
Style 20874 Bonded Flat Ribbon Cable.

Rating105 deg C, 60 Vac, Horizontal flame.
Conductor36 AWG - 20 AWG round or flat, solid or stranded round, tinned or bare copper.
InsulationOn each side of the conductors 1 mil minimum at any point. Polyester bonded together with minimum 25 mil insulation width on outside edges of conductors and 16 mil minimum width insulation between adjacent conductors.
AssemblyTwo through 100 conductors. Length of insulated conductors not specified.
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal wiring of electronic equipment in Class 2 circuits (such as computers and business machines).