Rating | 80 deg C, 600 Vac, Cable flame. |
|
Conductor | 16 AWG, stranded. |
|
Insulation | Extruded TPE, 20 mils minimum average thickness, 18 mils minimum thickness at any point. |
|
Assembly | Two through 60 individually insulated conductors or groups of insulated conductors to form a round cable. The length of lay of the twisted conductors or groups, shall be in accordance with Type SE under the Standard for UL 62. A barrier layer and/or fillers are optional. A barrier layer, if employed, may be a fibrous wrap serving, or braid; paper; nylon (polyamide); oriented polyethylene terephthalate; or thermoplastic-tape wrap. |
|
Jacket | Extruded TPU. |
| dia. in inches |
| 0.640 or less | 45 mils minimum average thickness | 36 mils minimum thickness at any point |
| 0.641-0.849 dia | 55 avg | 44 min |
| 0.850-1.000 dia | 65 avg | 52 min |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | External interconnection of electronic equipment where the acceptability of the combination is to be accepted by Underwriters Laboratories Inc. |
|