Rating | 80, 90, 105 deg C, 300 Vac, Cable flame. |
|
Conductor | 18-12 AWG, solid or stranded round, tinned or bare copper. |
|
Insulation | Labeled or complying with manufacturer's AWG procedure. |
|
Assembly | Two or three singles, laid parallel to form flat cable. Manufacturer shall maintain a complete description of each assembly. If two conductors are employed, they shall be black and white. If three are employed, the third shall be a grounding conductor green or green/yellow. |
|
Shield | Copper braid over the black and white conductor, 85 percent minimum coverage. Optional on grounding conductor. |
|
Jacket | PVC, 30 mils min average, 24 mils minimum at any point. |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | Internal wiring or external interconnection of electronic equipment where the acceptability of the combination is to be determined by Underwriters Laboratories. |
|