Rating | 105 deg C, 600 Vac, Cable flame, Oil Resistant 60 deg C or 80 deg C (optional). |
|
Conductor | 20 AWG - 2 AWG Stranded. Same as Type SE Cord. |
|
Insulation | TPE |
| 20-15 AWG conductor size | 30 mils min average | 27 mils minimum at any point |
| 14-10 AWG | 45 avg | 40 min |
| 8-2 AWG | 60 avg | 54 min |
|
Assembly | Two to sixty individually insulated conductors or groups of insulated conductors to form a round cable. The length of lay of the twisted conductors or groups is not, shall be in accordance with Type SE Cord under the Standard for Flexible Cord and Fixture Wire, UL 62. Fillers may be used in a cable but are not required. A barrier layer, if employed, may be a fibrous wrap serving, or braid; paper; nylon; oriented polyethylene terephthalate; or thermoplastic-tape wrap. |
|
Jacket | TPE |
| dia. in inhces |
| 0.500 or less | 80 mils min average | 64 mils minimum at any point |
| 0.501-0.750 dia | 95 avg | 76 min |
| 0.7501-1.000 dia | 110 avg | 88 min |
| 1.001-1.500 dia | 140 avg | 112 min |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | External interconnection of electronic equipment where the acceptability of the combination is to be accepted by Underwriters Laboratories Inc. |
|