APPLIANCE WIRING MATERIAL
Subj.758 Section 2 Page 20913 Issued:1996-03-20
Revised:2012-04-17
Style 20913 Multiple-conductor cable using non-integral jacket.

Rating60 deg C, 150 Vac, Cable flame.
InsulationLabeled or complying with Manufacturer's AWM Procedure.
AssemblyTwo or more individually insulated conductors or groups of insulated conductors laid parallel or cabled together to form a flat, oval or round cable. Conductors in any group twisted together. If more than one group is used, groups shall also be twisted together. The length of lay of the twisted conductors or groups is not specified. The use of a barrier layer and/or fillers is optional. Cable may contain Labeled Flat Ribbon Style AWM which may be rolled or spiralled and formed around fillers or bunched singles. Fillers and/or tape wrap or extruded covering may be used.
ShieldOptional - The shield may be over one or more of the insulated conductors or applied between the conductor assembly and the optional covering.
CoveringOptional - A 5 mils or heavier PVC covering may be extruded over one or more groups of conductors.
JacketExtruded PVC.
Diameter of core assembly under jacketMinimum average thicknessMinimum thickness at any point
0.700 inch or less30 mils24 mils
0.701-1.000 inch45 mils36 mils
1.001-1.500 inch60 mils48 mils
1.501-2.500 inch80 mils64 mils
2.501-4.000 inch110 mils88 mils
4.001 inch and larger140 mils112 mils
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal or external wiring.