Rating | 60 deg C, 150 Vac, Cable flame. |
|
Insulation | Labeled or complying with Manufacturer's AWM Procedure. |
|
Assembly | Two or more individually insulated conductors or groups of insulated conductors laid parallel or cabled together to form a flat, oval or round cable. Conductors in any group twisted together. If more than one group is used, groups shall also be twisted together. The length of lay of the twisted conductors or groups is not specified. The use of a barrier layer and/or fillers is optional. Cable may contain Labeled Flat Ribbon Style AWM which may be rolled or spiralled and formed around fillers or bunched singles. Fillers and/or tape wrap or extruded covering may be used. |
|
Shield | Optional - The shield may be over one or more of the insulated conductors or applied between the conductor assembly and the optional covering. |
|
Covering | Optional - A 5 mils or heavier PVC covering may be extruded over one or more groups of conductors. |
|
Jacket | Extruded PVC. |
| Diameter of core assembly under jacket | Minimum average thickness | Minimum thickness at any point |
| 0.700 inch or less | 30 mils | 24 mils |
| 0.701-1.000 inch | 45 mils | 36 mils |
| 1.001-1.500 inch | 60 mils | 48 mils |
| 1.501-2.500 inch | 80 mils | 64 mils |
| 2.501-4.000 inch | 110 mils | 88 mils |
| 4.001 inch and larger | 140 mils | 112 mils |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | Internal or external wiring. |
|