Rating | 105, 60 deg C, 300 Vac, Horizontal flame, Moisture Resistant 60 deg C, 720hr Sunlight Resistance. |
|
Conductor | 18 AWG - 10 AWG solid or stranded round, tinned or bare copper. |
|
Insulation | PVC |
| 18-12 AWG conductor size | 30 mils min average | 27 mils minimum at any point |
| 10 AWG | 45 avg | 40 min |
| See Facing Page for compound designation. |
|
Assembly | Two to five conductors, same as type SJT. Fillers, Binders - Optional. Strength Members - (Optional) unless needed to enable cord to comply with the mechanical strength test. |
|
Jacket | TPE - See Facing Page for compound designation |
| conductor size |
| 18-14 AWG | 30 mils min average | 24 mils minimum at any point |
| 12 AWG | 45 mils avg | 36 mils min |
| 10 AWG | 60 mils avg | 48 mils min |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | For use in internal or external power supply applications of electronic equipment in application requiring sunlight resistance and 60 deg. C water resistance where the use has been found acceptable by UL. (Similar to hard service cord Type SJEW except that PVC insulation is employed instead of TPE as specified under UL 62). |
|