|
Rating | 60, 75, 90, 105 deg C, 600 Vac, Horizontal flame, Oil Resistant 60 deg C. |
|
Conductor | 18-2 AWG consisting of 40 AWG stranding, tinned or bare copper. Aramid fiber strength member may be employed as a central member in stranded conductors. |
|
Insulation | PVC, 45 mils min average, 40 mils minimum at any point. |
|
Assembly | Two or more conductors, same as type STO. |
|
Jacket | PVC, 80 mils min average, 64 mils minimum at any point. |
|
Misc. | Aramid fiber strength member - Optional. |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | Internal or External Wiring of Electronic Equipment where exposed to oil at a temperature not exceeding 60 deg. C, and where the final acceptability is to be determined by Underwriters Laboratories. |
|