| Rating | 60 deg C, 300 Vac, Horizontal Flame. |
|
| Conductor | 30 AWG - 16 AWG solid or stranded. |
|
| Insulation | Extruded PE or FRPE, 15 mils min average thickness, 13 mils minimum thickness at any point. |
|
| Assembly | Two or more insulated conductors, twisted pairs or groups of twisted insulated conductors twisted together. The insulated conductors or groups of insulated conductors may be laid parallel forming a flat, oval or round cable. The lay of the insulated conductors is not specified. A barrier layer and/or fillers are optional. Manufacturer shall maintain a complete description of each assembly. May use same or mixed AWG size. Assembly insulated conductors with optional covering, optional shield, required jacket and optional wire braid. |
|
| Covering | Optional. A 6 mil or heavier PVC covering may be extruded over the insulated conductor assembly. |
|
| Shield | Optional. |
|
| Jacket | Extruded PVC. |
| Diameter of core assembly under jacket* | Minimum average thickness | Minimum thickness at any point |
| 0.350 inch or less | 15 mils | 12 mils |
| 0.351-0.700 | 30 mils | 24 mils |
| 0.701-1.000 | 45 mils | 36 mils |
| 1.001-1.500 | 60 mils | 48 mils |
| *Major diameter if cable is flat or oval. |
|
| Shield | Optional. Wire Braid. |
|
| Standard | Appliance Wiring Material UL 758. |
|
| Marking | General. |
|
| Use | Internal wiring of electronic equipment. |
|