APPLIANCE WIRING MATERIAL
Subj.758 Section 2 Page 2094 Issued:1959-05-01
Revised:2011-08-31
Style 2094 Multiple-conductor cable using non-integral jacket

Rating60 deg C, 300 Vac, Horizontal Flame.
Conductor30 AWG - 16 AWG solid or stranded.
InsulationExtruded PE or FRPE, 15 mils min average thickness, 13 mils minimum thickness at any point.
AssemblyTwo or more insulated conductors, twisted pairs or groups of twisted insulated conductors twisted together. The insulated conductors or groups of insulated conductors may be laid parallel forming a flat, oval or round cable. The lay of the insulated conductors is not specified. A barrier layer and/or fillers are optional. Manufacturer shall maintain a complete description of each assembly. May use same or mixed AWG size. Assembly insulated conductors with optional covering, optional shield, required jacket and optional wire braid.
CoveringOptional. A 6 mil or heavier PVC covering may be extruded over the insulated conductor assembly.
ShieldOptional.
JacketExtruded PVC.
Diameter of core assembly under jacket*Minimum average thicknessMinimum thickness at any point
0.350 inch or less15 mils12 mils
0.351-0.70030 mils24 mils
0.701-1.00045 mils36 mils
1.001-1.50060 mils48 mils
*Major diameter if cable is flat or oval.
ShieldOptional. Wire Braid.
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal wiring of electronic equipment.